User's Manual

Cabinet Mounting
continued
Apr 2001
V04.03
77
SC
TM
4812ET RF and Power Cabinet Hardware Installation Manual
DRAFT
A string of batteries consists of two (2) batteries connected
in series. The Power Cabinet can accommodate up to
twelve (12) strings of batteries.
NOTE
All AC and DC power should be removed from the
system until all connections are made.
Ensure that all of the battery string breakers are off
(white the strip on the bracket is visible), there are a
total of 12 battery string circuit breakers.
WARNING
Materials Needed
Table 4-7 lists the necessary materials. Quantities will be determined by
system configuration.
Table 4-7: Materials Required for Battery Cabling
Qty per
String
Description
1 Battery Terminal Strap (supplied with the Installation
Hardware)
4 Fasteners, 2 per Battery (supplied with Batteries)
1 Wire Brush
As Required Copperbased conductive Grease (Berndy Penetrox or
equivalent).
Power Cabinet Battery Cabling Procedure
This procedure is used to cable and connect a string of batteries in the
Power Cabinet, it should be repeated until all batteries have been
installed.
This procedure assumes the batteries have already been
installed.
NOTE
Table 4-8: Power Cabinet Battery Cabling
Step Action
1 Clean battery terminals with a wire brush.
2 Apply liberal coating of conductive grease to all battery terminals,
. . . continued on next page
4