Site Preparation continued
Apr 2001
45
SC
TM
4812ET RF and Power Cabinet Hardware Installation Manual
DRAFT
The Power Cabinet is rated at 130 Amps (100 Amps
continuous / 130 Amps noncontinuous, in the range of
208240V AC, see Table 5-32 for details). Maximum
cable size that can be accommodated is 300 kc mil.
Cabling sizing should be determined by Local Electrical
Codes, using 90Deg C rated conductors, and derated for
50 Deg C operation. Motorola recommends not less than
#2/0 AWG (#1 BSWG; 50 mm
2
) copper for
buried/raceway cables to the power pedestal, with an
associated power pedestal breaker size of 150 Amps for
one Power Cabinet.
IMPORTANT
*
The AC power pedestal or meter should be provided with a breaker to
protect the cable from the pedestal to the Power Cabinet. The Power
Cabinet rating is 130Amp. A 150amp breaker is recommended, or as
appropriate for local electrical code.
The knockout in the I/O plate of the Power Cabinet is the
proper size for a 2 Trade size conduit fitting.
NOTE
Ground Wire Connection (RF and Power Cabinet) #3 B.S.W.G (#2
AWG; 35 mm
2
) solidtinned copper wire or equivalent is recommended
RF Cabinet Alarm Cable Connection
Sixteen (16) twisted pair cable
25.4 mm (1) conduit (maximum)
RF Cabinet Span and Modem Cable Connection
Thirteen (13) twisted pair cable
25.4 mm (1) conduit (maximum)
Main RF Cable 50 Ohm Coaxial, male Ntype connector on one end,
customer specific on other end.
RGPS Cable (if applicable) See Table 5-1 for cable specifications
RF GPS Cable (if applicable) See Table 5-1 for cable specifications
LFR Cable (if applicable) See Table 5-1 for cable specifications
. . . continued on next page