User's Manual

Introduction
continued
Apr 2001
V02.03
31
SC
TM
4812ET RF and Power Cabinet Hardware Installation Manual
DRAFT
Figure 1-10: Minimum Site Clearances for SC 4812ET Cabinets
NOTE:
(1) 24 IS RECOMMENDED BETWEEN CABINETS TO ALLOW
SIMULTANEOUS OPENING OF CABINET DOORS
(2) BASED ON FIGURE 110 MOTOROLA RECOMMENDS A MINIMUM
PAD (OR PEDESTAL) SIZE OF 2515 MM (99) BY 3710 MM (146)
130 mm
(5)
130 mm
(5)
330 610 mm
(13 24)
660 mm
(26)
1143 mm
(45)
3430 3710 mm
(135 146)
2515 mm
(99)
660 mm
(26)
1143 mm
(45)
Power
Cabinet
RF Cabinet
FW00105
1