Installation Instructions
Power, Ground and Battery Cabling for Sites Equipped With Optional
Primary Surge Suppressor
– continued
DEC 2000
5-13
SCt300 BTS Hardware Installation, ATP and FRU Procedures
PRELIMINARY
Cables Needed
Table 5-2 provides the quantity and description of the cables needed.
Table 5-2: Cables Needed for Power, Earth Ground, and Battery Connections
Cable Qty. Part Number Description
A 1–4 3087701C02 Ground cable, 8 -AWG, insulated copper wire. Requires one ring lug
connector.
S 1–4 3087854C02 AC input cable, 14 AWG, 5 m, is designed for 88–260 VAC power
input. Cable has Deutsch connector on both ends.
T 1 Customer
Supplied
AC Input power cable. 10–14 AWG, 90_C wire. Designed for
120–240 VAC.
U 1–4 3087854C04 DC input cable, 14 and 22 AWG, 5 m, is designed for 20 to 30 VDC
power input.
Y 1 Customer
Supplied
Master Ground Cable, 6 -AWG, insulated copper wire.
AC Input Cable Information
The information for the AC input cable(s) (Cable S) is given in
Figure 5-10 and Table 5-3.
Figure 5-10: AC Input Cable Connector Information
A
B
C
SOCKET POSITION ON CABLE
CONNECTOR SHOWN
Table 5-3: AC Input Cable Information
Connector Wire Color Description
A Black Line
B Green Ground
C White Neutral