Installation Instructions

Power, Ground, and Battery Cabling for Sites Equipped With
Customer–Supplied Site I/O Interface
– continued
DEC 2000
4-17
SCt300 BTS Hardware Installation, ATP and FRU Procedures
PRELIMINARY
Cables Needed
Table 4-14 provides the quantity and description of the cables needed.
Table 4-14: Cables Needed for Power, Earth Ground, and Battery Connections
Cable Qty. Part Number Description
S 1–4 3087854C02 AC input cable, 14 AWG, 5 m, is designed for 88–260 VAC power
input.
U 1–4 3087854C04 DC input cable, 14 and 22 AWG, 5 m, is designed for 20 to 40 VDC
power input.
Y 1–4 Customer
Supplied
Ground cable, 6 -AWG, insulated copper wire. Requires one ring lug
connectors.
AC Input Cable Information
The pinout information for the AC input cable(s) (Cable S) is given in
Figure 4-9 and Table 4-15.
Figure 4-9: AC Input Cable Connector Information
A
B
C
SOCKET POSITION ON CABLE
CONNECTOR SHOWN
Table 4-15: AC Input Cable Information
Connector Wire Color Description
A Black Line
B Green Ground
C White Neutral
4