User Manual

Power Cabinet Initial Power Up – continued
PRELIMINARY 2
SC 4812ET BTS Optimization/ATP – CDMA LMF
July 1999
2-12
Table 2-15: Multiple Rectifier Failure or Major Alarm
Step Action
4 Turn the AC breaker for this shelf ON. Verify that all alarms have cleared.
5 Return all rectifier module to their original location. This completes the rectifier alarm tests on the
Power Cabinet.
Battery Over Temperature
Alarm (Optional ONLY)
Use special care to avoid damaging insulation on cables, or
damaging battery cases when using a power heat gun.
CAUTION
Table 2-16 gives instructions on testing the battery over temperature
alarm system.
Table 2-16: Battery Over Temperature Alarm
Step Action
1 Use a low powered heat gun and gently heat the battery over temperature sensor. Do Not hold the
hot air gun closer than three (3) inches to the sensor. This will avoid burning the cable insulation.
2 When the sensor is heated to approximately 50° C, a battery Over Temperature alarm is generated.
NOTE
An auditable click will sound as K1 contacts engage and K2 contacts disengage.
3 Visually inspect the K1 and K2 relays to verify state changes. The LMF should be displaying
correct alarms. Alarm condition will be reported as BTS–22 contact.
4 Verify that the CHARGE DISABLE LED (amber) on the DMAC and the BATTERY MAIN LED
(green) are both illuminated.
5 Switch the hot air gun to cool. Cool the sensor until the K1 and K2 contact return to normal
position (K1 open and K2 closed). Using the LMF verify that all alarms have cleared.
2