Customer Alarm Input Verication
Procedure E -4 describes how to test the Customer alarm input verification. F ollow the steps as
instructed and compare results with the LMF display .
It may take a few seconds for alarms to be reported. The default delay is 5 seconds.
When shorting alarm pins wait for the alarm report before removing the short.
Procedure E -4 Customer Alarm Input V erication
1
Connect the LMF to the UBS and log into the UBS .
2
Select the Controller .
3
Click on the Device menu.
4
Click on the Set Alarm Relays menu item.
5
Click on Normally Open .
A status report window displays the results of the action.
6
Click on OK to close the status report window .
7
Refer to Figure E -2 and sequentially short the ALARM
A connector CA IN 1 through CA IN 12 pins together .
Sequentially short the ALARM B connector
CA IN 13 through CA IN 24 pins together .
An alarm should be reported for each pair of pins that are shorted.
A clear alarm should be reported for each pair of pins when the short
is removed.
8
Select the Controller .
9
Click on the Device menu.
10
Click on the Set Alarm Relays menu item.
1 1
Click on Normally Closed .
A status report window displays the results of the action.
12
Click on OK to close the status report window .
Alarms should be reported for alarm inputs 1 through
24.
13
Sequentially short the ALARM B connector
CA IN 13 through CA IN 24 pins together .
A clear alarm should be reported for each pair of pins that are shorted.
An alarm should be reported for each pair of pins when the short is removed.