Installation Manual

Site v erication Chapter 2: UBS Macro B T S Installation Procedure
Table 2 -8 +27 V DC and –48 V DC Fr ame P ower Cabling and P ower Supply Break er
Information (Continued)
Qty of XMIs
Maximum
cable length
Cable
size
(A WG)
Cable insulation
temperature rating
C)
Qty of power
feeds (+ and
- pairs)
Breaker size per
feed (Amps DC)
4 661.11 cm
(21.69 ft)
2/0 200 2 250
4 833.63 cm
(27.35 ft)
3/0 150 2 250
4 1051.25 cm
(34.499 ft)
4/0 150 2 250
Frame positioning
Typically , equipment frames are positioned side -by -side, with the frame fronts facing the same
direction.
Rack base description and dimensions
The base of the rack consists of the following:
Isolation pads attached to the base to isolate the rack from the floor . The isolation pads are
positioned between the floor and the base.
Six 22 mm (0.87 inches) M12 mounting holes.
Plastic shoulder washer in each hole to isolate the frame from the floor . Figure 2 -5 shows
the footprint of the rack.
2 -18 68P09283A62 -3