User's Manual Part 1

Site Inspections – continued
PRELIMINARY
1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU
MAY 2004
2-4
Grounding Inspections
Indoor installations
For indoor installations refer to the Grounding Guideline for Cellular
Radio Installations (68P81150E62) for all grounding inspection
procedures.
Verify the following:
S All ground cables have a bend radius of 20 cm (8 inches) or more.
S Metallic lines (span, phone[modem], RGPS, power and antenna) that
enter or leave the site should be equipped with a 3-electrode gas tube
protector. The ground side of the gas tubes should be tied to the
Master Ground Bus (MGB).
S All installed cable racks (in the same ground zone) are jumpered
together.
Cable racks in an Isolated Ground Zone (IGZ) are not to be
connected to a cable rack in a non-IGZ. For more
information on IGZ, see Grounding Guideline for Cellular
Radio Installations, Motorola part number 68P81150E62
or Appendix C of Standards and Guidelines for
Communications Sites (Motorola part number
9882904Y01)
WARNING
Outdoor Installations
For outdoor installations refer to the Grounding Guideline for Cellular
Radio Installations (Motorola part number 68P81150E62) or Appendix
C of Standards and Guidelines for Communications Sites (Motorola part
number 9882904Y01) for all grounding inspection procedures.
Verify the following:
S All outdoor enclosures are grounded to system masrter ground.
S All enclosures have conduit attached.
S It is recommended that all metallic lines (span, RGPS, power, and
antenna) that enter or leave the site are be equipped with a surge
suppression device (lightning arrestor).
2