User's Manual Part 1
Power Distribution Enclosure Installation – continued
PRELIMINARY
1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU
MAY 2004
4-38
Table 4-20: Procedure to Install the Wall Mounting Bracket on a Wall
Step Action
1 Select a suitable wall position such that the bottom of the PDE is a minimum of 1 meter above the
ground.
NOTE
Check site documentation for further information.
2 Position Wall Mounting Bracket on wall and mark hole locations.
3 Drill starter holes for the anchor bolts.
4 Secure Wall Mounting Bracket to wall using 8 M6 anchor bolts. Torque anchor bolts to 3.4 N–M (30
in–lbs).
5 Unlock and open PDE side door and remove Power Converter.
NOTE
Screw to secure PDE to Wall Mounting Bracket can only be seen with Power Converter removed.
n WARNING
The PDE (less HX) weighs 25 kg (55 lbs) . It is recommended that a minimum of two people or one
person using a mechanical lift mount the PDE.
Remove Heat Exchanger prior to mounting the PDE.
6 Hang PDE on Wall Mounting Bracket.
7 Secure PDE to Wall Mounting Bracket using 4 M6 screws. Torque screws to 3.4 N–M (30 in–lbs). See
Figure 4-26.
8 Install Power Converter after PDE is secure to Wall Mounting Bracket.
Figure 4-26: PDE Mounting Screw Locations
Screw Hole Location
Screw can only be inserted if the
Power Converter is first removed.
4