Discharge Test
Perform the test procedure in Table 2-9 only when the battery current is
less than 5 A per string. Refer to Table 2-8 for the procedures to check
current levels.
Table 2-9: Battery Discharge Test
Step Action
1 Turn the battery test switch on the Meter Alarm Panel, ON (see Figure 2-3). The rectifier output
voltage and current should decrease by approximately 10% as the batteries assume the load. Alarms
for the Meter Alarm Panel may occur.
2 Measure the individual battery string current using the DC current probe. The battery discharge
current in each string should be approximately the same (within± 5 A).
3 Turn Battery Test Switch OFF.
CAUTION
Failure to turn OFF the Battery Test Switch before leaving the
site, will result in low battery capacity and reduce battery life.