Alarms Testing – continued
Jan 2002
3-111
SC4812ET BTS Optimization/ATP — CDMA LMF
Multiple Rectifier Failure
Table 3-59 gives instructions on testing multiple rectifier failure or major
alarm in a three rectifier system.
Table 3-59: Multiple Rectifier Failure or Major Alarm
Step Action
1 With the rectifier module still in the unused shelf position fromTable 3-58 test procedures, turn the
AC breaker for the 1st shelf OFF.
2 Verify that a rectifier alarm is generated. Each of the two rectifier modules will lite two RED fail LED
(DC and Power), and the Meter Alarm Panel and LMF will indicate a major alarm (Rectifier Fail and
Major Alarm). The RECTIFIER FAIL LED will lite.
3 Verify that the LMF reports both alarm conditions. (BTS #29, BTS #21, and BTS #24)
4 Turn the AC breaker for the 1st shelf ON. Verify that all alarms have cleared.
5 Return the rectifier module to its original location. This completes the alarm test on the power cabinet.
Single Rectifier Failure
(Six Rectifier System)
Table 3-60 gives instructions on testing single rectifier failure or minor
alarm in a six rectifier system.
Table 3-60: Single Rectifier Fail or Minor Alarm
Step Action
1 Remove two(2) rectifier modules from shelf #2.
2 Turn the AC breaker OFF, for shelf #2.
3 Verify that a rectifier fail alarm is generated. The single rectifier module will lite two RED fail LED
(DC and Power), and the Meter Alarm Panel and LMF will also indicate a minor alarm and rectifier
fail status. The RECTIFIER FAIL LED will lite.
4 Check that the LMF reports both of these alarm conditions. (BTS #24 and BTS #21)
5 Turn the AC breaker for this shelf ON and verify that Rectifier Fail and Minor Alarm conditions have
cleared.
3