1-22
50-pair Punchblock
The 50-pair punchblock (Figure 1-5) is the interface between the frame
and the T1/E1 span lines. It is located on the right-hand side of the
power entry compartment at the rear of the frame. The punchblock
provides the initial interconnection between the spans and the
Customer-defined I/O, alarms, multi-frame timing source (Remote GPS
and HSO), and pilot beacon control (optional).
Figure 1-5: 50-Pair Punchblock
Rear of Frame
(Power Entry Compartment
Door Open)
Section of Network Interface Panel
(Rotated 30 Right)
50-pair
Punchblock
(Cabling not
shown for
clarity)
SC4812ETL0024-2
AC Load Center (ACLC)
The ACLC is the frame entry point for AC power. It incorporates AC
power control, distribution, and surge protection (Figure 1-3). Two
versions are available, depending on the type of AC input power
available at the operating site:
1. International
2. North American
Back-up Batteries
The batteries (Figure 1-3) provide +24 Vdc back-up for the frame should
AC power be interrupted. The frame can accommodate a total of 12 12V
batteries grouped in six strings. Each string consists of two batteries
connected in series for 24 Vdc output. The six strings are connected in
parallel to meet the current-draw requirements of the frame. The
maximum time duration of the back-up capability depends on system
configuration.