User's Manual

Table Of Contents
BTS Redundancy/Alarm Testing68P09255A61-4
Aug 2002
1X SC 4812T BTS Optimization/ATP Software Release 2.16.1.x
FIELD TRIAL
3-93
Figure 3-23: -48 V BTS Power Conversion Shelf
FW00501
PS-6
AMR
PS-5
PS-4
PS-9
PS-8
PS-7
1C
1A
2A
2C
3C
3A
4A
4C
L
P
A
1D
1B
2B
2D
3D
3B
4B
4D
30
30
30
30
30
30
30
30
FAN
MODULE
PWR/ALM
REAR
FRONT
FAN
MODULE
PWR/ALM
REAR
FRONT
Miscellaneous Alarm/Redundancy Tests
Follow the steps in Table 3-50 to verify alarms reported by the master
GLI are displayed via the alarm monitor if a BTS frame module failure
occurs.
Table 3-50: Miscellaneous Alarm Tests
Step Action
1 Select Util>Alarm Monitor to display the alarm monitor window.
2 Perform the following to verify fan module alarms:
Unseat a fan module (see Figure 3-24 or Figure 3-25).
Observe an alarm message was reported via the MGLI (as displayed on the alarm monitor).
Replace fan module and verify the alarm monitor reports that the alarm clears.
Repeat for all other fan modules in the BTS frame.
NOTE
Follow Step 3 for Starter Frames and Step 4 for Expansion Frames.
3 Starter Frames Only:
Perform the following to verify MPC module alarms.
Unseat MPC modules (see Figure 3-22) one at a time.
Observe that an alarm message was reported via the MGLI as displayed on the alarm monitor.
Replace the MPC modules and verify the alarm monitor reports the alarm clears.
4 Expansion Frames Only:
Perform the following to verify EMPC module alarms.
Unseat EMPC modules (see Figure 3-22) one at a time
Observe that an alarm message was reported via the MGLI as displayed on the alarm monitor.
Replace the EMPC modules and verify the alarm monitor reports that the alarm clears.
. . . continued on next page
3