User's Manual Part 3

Alarms Testing continued
Apr 2001
3-83
SC4812ET BTS Optimization/ATP CDMA LMF
DRAFT
Heat Exchanger Alarm Test
Table 3-46 gives instructions on testing the Heat Exchanger alarm.
Table 3-46: Heat Exchanger Alarm
Step Action
1 Turn circuit breaker B of the Heat Exchanger circuit breakers OFF. This will generate a Heat
Exchanger alarm, ensure that the LMF reports the correct alarm condition in the RF Cabinet.
2 Alarm condition will be reported as BTS Relay #25 Heat Exchanger Alarm makes contact.
3 Turn the circuit breaker B ON. Ensure that the alarm condition is now removed.
NOTE
The Heat Exchanger will go through the Start Up sequence.
Door Alarm
Table 3-47 gives instructions on testing the door alarms.
Table 3-47: Door Alarm
Step Action
1 Close all doors on the power cabinet. Ensure that no alarms are reported on the LMF.
2 Individually open and then close each power supply cabinet door. Ensure that the LMF reports an
alarm when each door is opened.
3 Alarm condition will be reported as BTS Relay #27 Door Alarm makes contact.
AC Fail Alarm
Table 3-48 gives instructions on testing the AC Fail Alarm.
Table 3-48: AC Fail Alarm
Step Action
1
NOTE
The batteries should have a stable charge before performing this test.
Turn the Main AC breaker on the power cabinet OFF. The LMF should report an alarm on an AC Fail
(Rectifier Fail, Minor Alarm & Major Alarm) condition.
2 Alarm condition will be reported as BTS Relay #23, BTS # 21, BTS # 24 and BTS Relay # 29 AC
Fail Alarm makes contact respectively.
3 Turn the Main AC breaker on the power cabinet ON. The AC Fail alarm should clear.
3