Manual
FRU Optimization/ATP Test Matrix
68P09258A31–A
Oct 2003
1X SCt 4812T BTS Optimization/ATP
C-4
Table C-3: SC 4812T BTS Optimization and ATP Test Matrix
Doc
Tbl
#
page
Description
Directional Coupler (RX)
Directional Coupler (TX)
RX Filter
RX Cables
TX Cables
MPC/EMPC
CIO
C–CCP Backplane
BBX
MCC
CSM
LFR/HSO
GPS
GLI
LPA Trunking Backplane
LPA
LPA Bandpass Filter
Power Supply Modules
Switch Card
RFDS
Table 2-1 2-3
Initial Boards/Modules Install,
Prelimnary Operations, CDF
Site Equipage; etc.
D D D D D D D D D D D D D D D D D
D
**
D D
Table 2-2
Table 2-5
2-6
2-14
DC Power Pre-Test Physical
Inspect
D D
Table 2-7 2-15
Initial Power-up
D D D
D
**
D
Table 3-11 3-34
Ping the Processors
D D D D D D
Table 3-13 3-38
Download/Enable MGLIs
D D D
Table 3-13 3-38
Download/Enable GLIs
D D D
Table 3-14 3-39
Download CSMs
D D D D
Table 3-14 3-39
Download MCCs
D D D D
Table 3-14 3-39
Download BBXs
D D D
Table 3-16 3-41
Enable CSMs
D D
Table 3-17 3-42
Enable MCCs
D D
Table 3-20 3-49
GPS Initialization /
Verification
D D D
Table 3-21 3-53
LFR Initialization /
Verification
D D
Table 3-22
3-55
HSO Initialization/Verification
D D
D Required
** Replace power converters one card at a time so that power to the C–CCP or LPA shelf is not lost. If power to
the C–CCP shelf is lost, all cards in the shelf must be downloaded again.
C