Installation Instructions
System Requirements for Installation and Operation
32 (43) © Nokia Corporation DN00283911
Nokia Proprietary and Confidential Issue 2 DRAFT 1 - en
Note
Note
• 220 VAC
• -48 VDC
4.6.3 Power consumption
The power consumption of the MU is dependent on the RU configuration.The
consumption of the MU is less than 100 W.
The power consumption of one RU is 15 W.
4.6.4 Connectors, cables and fuses for cable protection
A prefabricated mains power cable for the RU is supplied by Nokia.
If you use the prefabricated mains power cable supplied by Nokia, make sure that
the power distribution box (mains power supply) is located no further than 10
metres from the Nokia InLite MU.
Table presents the requirements for the RU power supply cables, connectors and
the recommended mains fuses.
Power
supply
type
Connector
type at the
end of cable
Cable
Recommended
fuse for cable
protection
AC supply
220V
IEC 320
(female)
Multicore cable 3 x
0.75 to 1.5 mm
2
10A for 1.5 mm
2
6A for 0.75 mm
2
AC supply
110V
IEC 320
(female) with
notch
Multicore cable 3 x 1.5
mm
2
10 A
DC supply
-48V
(optional)
Bayonet
(female)
Composite fibre optic/
copper cable, twinfibre,
2x15mm
2
-