Nokia MetroSite GSM Base Station, Requirements for Installation and Operation DN9913471 © Nokia Networks Oy Issue 1 en DRAFT 2 Draft Internal Copy 1 (38)
Nokia MetroSite GSM Base Station, Requirements for Installation and Operation The information in this document is subject to change without notice and describes only the product defined in the introduction of this documentation. This document is intended for the use of Nokia Networks' customers only for the purposes of the agreement under which the document is submitted, and no part of it may be reproduced or transmitted in any form or means without the prior written permission of Nokia Networks.
Contents Contents 3 1 About this document 7 2 2.1 2.1.1 2.1.2 2.1.3 2.2 2.2.1 2.2.2 2.2.3 2.3 2.3.1 2.3.2 2.3.3 2.3.4 2.3.5 2.3.6 2.3.
Nokia MetroSite GSM Base Station, Requirements for Installation and Operation 4 (38) © Nokia Networks Oy Internal Copy DN9913471 Issue 1 en DRAFT 2 Draft
Summary of changes Version 1, 12th November 1999. Pilot 3 (Version 1.2), 6th April 2000: • Added GSM to title and to body text • Added CE marking • Changed acoustic noise to 61dB in Chapters 2.3.5, 3.6.2 and Figure 5 • Increased cabinet length to 870mm in Figures 1 and 2.
Nokia MetroSite GSM Base Station, Requirements for Installation and Operation 6 (38) © Nokia Networks Oy Internal Copy DN9913471 Issue 1 en DRAFT 2 Draft
About this document 1 About this document This document introduces the requirements set by the Nokia MetroSite GSM Base Station (BTS) for successful installation and operation.
Nokia MetroSite GSM Base Station, Requirements for Installation and Operation 8 (38) © Nokia Networks Oy Internal Copy DN9913471 Issue 1 en DRAFT 2 Draft
Environment 2 Environment This chapter defines the classes of environmental conditions and their severities to which the Nokia MetroSite GSM BTS can be exposed. The information is organised in the following parts: 2.1 • Conditions for Storage • Conditions for Transportation • Conditions for Operation Storage This section defines the environmental conditions which the Nokia MetroSite GSM BTS can be exposed to during storage.
Nokia MetroSite GSM Base Station, Requirements for Installation and Operation Table 1. Climatic conditions for storage Environmental parameter Value Low air temperature - 25 °C - 13 °F 55 °C High air temperature 131 °F Low relative humidity 10% High relative humidity 100% Low absolute humidity 0.5 g/m3 High absolute humidity 29 g/m3 Rain intensity none Temperature change rate (average of 5 minutes) 0.5 °C/min 0.9 °F/min Low air pressure 70 kPa 10.15 psi High air pressure 106 kPa 15.
Environment 2.2 Transportation This section defines the environmental conditions which the Nokia MetroSite GSM BTS can be exposed to during transportation. Caution The Nokia MetroSiteGSM BTS must be transported in its original package before the installation. Note The Nokia MetroSite GSM BTS is delivered to the customer with the ordered plug-in units preinstalled. 2.2.
Nokia MetroSite GSM Base Station, Requirements for Installation and Operation Table 2.
Environment 2.2.3 Mechanical conditions for transportation For mechanical conditions during transportation, the Nokia MetroSite GSM BTS complies with ETS 300 019 1-2:1992 class 2.2. 2.3 Operation This section defines the environmental conditions during the operation of the Nokia MetroSite GSM BTS at locations which are not protected from direct weather influences. Note When surveying the prospective sites, consider the values presented in this section.
Nokia MetroSite GSM Base Station, Requirements for Installation and Operation Table 3. Climatic conditions for operation (Class 4.1, partly extended) Environmental parameter Class 4.1 value Extended value for Nokia MetroSite BTS Low air temperature -33°C -40 °C -27°F -40 °F 40 °C 50 °C 104°F 122 °F Low relative humidity 15% - High relative humidity 100% - Low absolute humidity 0.26 g/m3 0.
Environment 2.3.3 Mechanical conditions for operation For mechanical conditions during operation, the Nokia MetroSite GSM BTS complies with ETS 300 019-1-4:1992 class 4.1. 2.3.4 Ingress protection The electronic components inside the units of the Nokia MetroSite GSM BTS are protected against the ingress of rain, snow and dust to the minumum level of IP55 of European standard EN 60529, and level 3R of UL standard 50. 2.3.
Nokia MetroSite GSM Base Station, Requirements for Installation and Operation 16 (38) © Nokia Networks Oy Internal Copy DN9913471 Issue 1 en DRAFT 2 Draft
Installation requirements 3 Installation requirements This chapter specifies the preparatory requirements for the installation of the Nokia MetroSite GSM BTS. 3.1 Checking the site The cabinet installation phase requires that the site be properly surveyed and prepared, and that all required external services are correctly installed. The site survey must identify any special requirements for the installation. The site must meet the following requirements before the installation can be started: 3.2 1.
Nokia MetroSite GSM Base Station, Requirements for Installation and Operation 3.2.1 Nokia MetroSite BTS dimensions and weight Figure 1 presents the dimensions of the Nokia MetroSite GSM BTS. 870 mm (34.25 in) 114 mm (4.49 in) 310 mm (12.20 in) Figure 1. 215 mm (8.46 in) Dimensions of Nokia MetroSite BTS cabinet The Nokia MetroSite GSM BTS with four TRXs weighs approximately 40 kg (88.4 lb). The mounting rack weighs approximately 2 kg (4.4 lb).
Installation requirements Min 50 (2.0) 260 (10.2) 260 (10.2) 245 (9.65) NOTE: DIMENSIONS mm (inch) Top view 260 (10.2) 235 (9.3) 235 (9.3) 235 (9.3) 100 (3.94) 100 (3.94) 100 (3.94) 300 (11.9) 300 (11.9) 480 (18.9) 1270mm (50 in) 870mm (34,25 in) Front view 300 (11.9) DN9977591 310 (12.2) Figure 2. Clearances around Nokia MetroSite BTS The packing cardboard provides a template for defining the clearances around the BTS and for marking the drilling holes needed for wall mounting.
Nokia MetroSite GSM Base Station, Requirements for Installation and Operation • For removing units on the right-hand side of the BTS • For removing the cover above the BTS • For hanging the cover on the left-hand side of the BTS • For cables and for cooling under the BTS Note In order to hang the cover on the side of the cabinet during installation and maintenance, a clearance of 250 mm (10 in) is required.
Installation requirements A) Vertical mounting Figure 3. B) Horizontal mounting Mounting of Nokia MetroSite BTS Note If there is a risk that lumps of snow or pieces of ice can fall onto the BTS (from the antenna or microwave radio pole, for example), an effectual roof must be mounted to shield the BTS.
Nokia MetroSite GSM Base Station, Requirements for Installation and Operation 3.4 Requirements for wall and pole installation Qualified personnel must inspect the installation wall and/or pole before mounting the BTS. Ensure that the installation wall or pole is strong enough to bear the weight of the BTS (max. 40 kg / 88.4 lb) in any condition. The optional pole mounting kit can be used when the installation pole diameter is between 60 and 300 mm (2.36 and 11.81 in).
Installation requirements A power plug with protective ground connection is not sufficient for Nokia MetroSite BTS. Grounding must have a fixed, non-removable connection.
Nokia MetroSite GSM Base Station, Requirements for Installation and Operation 3.6 Mains power WARNING The power switch on the power supply unit of the Nokia MetroSite GSM BTS does not disconnect it from the power network (AC or DC), but leaves it in a stand-by mode. The switch has two positions: ON and stand-by. A separate main switch on the site is considered a disconnect device for safety and service purposes. Follow the national legislation when working with the power supply.
Installation requirements • BTS configuration • Ambient temperature • Direction of the temperature change The power consumption is higher when the ambient temperature is decreasing and the heating power of the BTS is increasing. When the ambient temperature is rising, the heating power is reducing. Consequently, the power consumption of the Nokia MetroSite GSM BTS in a given temperature varies according to the direction of temperature change.
Nokia MetroSite GSM Base Station, Requirements for Installation and Operation 3.6.2 Acoustic sound power The fan unit of the Nokia MetroSite GSM BTS generates acoustic noise. The level of acoustic sound power is dependent on the following factors: • Ambient temperature • Rate of the temperature change • Ouput power The acoustic sound power level is higher when the ambient temperature is changing rapidly. Refer to Figure 5 for the range of acoustic sound power level in different ambient temperatures.
Installation requirements 3.6.3 Connectors, cables and fuses for cable protection Note Prefabricated mains power cables can be ordered from Nokia. Note If you use the prefabricated mains power cable supplied by Nokia, make sure that the power distribution box (mains power supply) is located no further than 10 metres from the BTS’s power supply unit. Table 6 presents the requirements for power supply cables and the recommended mains fuses. Table 6.
Nokia MetroSite GSM Base Station, Requirements for Installation and Operation 3.7 Painting the BTS cover If desired, the BTS cover can be painted to make it better blend into the surrounding environment. Nokia recommends that for painting the cover a primer-topcoat combination of Beckers TD 130 primer (for priming) and Beckers TH 141 paint (for surface painting) be used. Other paints suitable for polycarbonate surfaces may also be used.
Installation requirements Figure 6. Removing the cover top 3. Remove stains and dust from the surface of the cover with an alcoholic or acidic wash, or wipe it clean with a piece of cloth moistened with water and mild washing agent. Do not use washing agents that contain alkalis, aromatic, chlorinated, or fluorinated hydrocarbons, esters or ketones. 4. Rinse with water to remove residuals of cleaning chemicals. 5.
Nokia MetroSite GSM Base Station, Requirements for Installation and Operation Figure 7. 8. Areas used for holding the cable cover parts during painting Spray paint over the outside surface of the cover. Spraying should be done at room temperature with relative air humidity of 50-65%. Note The maximum thickness of the paint should not exceed 100 µm. 9. Dry the parts either in an oven or let the paint dry at room temperature according to the paint manufacturer’s drying instructions.
Cabinet interfaces and cables 4 Cabinet interfaces and cables This chapter describes the external interfaces and interconnecting cables (excluding the grounding and power supply cables) for the Nokia MetroSite GSM BTS. Pin configurations for the relevant connectors can be found in Nokia MetroSite GSM Base Station: Product Description. Note Antenna line cables, LMP cable, Abis cables and Flexbus cables can be ordered from Nokia.
Nokia MetroSite GSM Base Station, Requirements for Installation and Operation Table 8. Transmission connectors of Nokia MetroSite BTS Transmission unit type Number of connectors Connector type Cable FC RRI 1 TNC 50 Ω Flexbus RG-223 (max length 140 m), Flexbus RG- 214 (max. length 300 m) For more information, refer to Nokia MetroSite GSM Base Station: Product Description.
Cabinet interfaces and cables 7-10 (.28-.39), 2 pcs Extension cables 8-12.5 (.31-.49), 4 pcs Antenna feeders 10-15 (.39-.59), 1 pc Power supply cable 4.5-7 (.18-.28), 14 pcs - Grounding cable, 1 pc - Transmission cables, max 8 pcs - External alarms and controls Figure 8.
Nokia MetroSite GSM Base Station, Requirements for Installation and Operation 34 (38) © Nokia Networks Oy Internal Copy DN9913471 Issue 1 en DRAFT 2 Draft
Installation equipment 5 Installation equipment This section specifies the equipment that is recommended for the installation of the Nokia MetroSite GSM BTS, but not included in the BTS delivery. Torque driver (0-6 Nm/0-5 ft-lb) with: - T10 Torx bit with min. 60 mm shaft for unit retaining screws (1.5 Nm/1.11 ft-lb) - 4 mm Allen bit with min. 60 mm shaft: A) for BTS fixing screws (5.5 Nm/4.06 ft-lb) B) for fixing cable entry block screws C) for fixing grounding cable (5.5 Nm/4.
Nokia MetroSite GSM Base Station, Requirements for Installation and Operation Additional equipment includes: • LMP cable for connecting the manager PC to the BTS • Antistatic wrist strap • Spirit level for checking the horizontal level of the BTS • Tape measure • Cable ties for routing the cables • Crimping tool for assembling the power supply cable connector (AC and DC) Note A set of tools needed for assembling the cable connectors is available at Nokia.
Index A acoustic noise 15, requirements for 17 installation equipment 35 installation space 17 interface connectors 31 26 C cable diameters 31, 33 cable entry block 32 cable protection 27 cables antenna feeders 32 extension 32 external alarms and controls grounding 32 power supply 32 transmission 32 types 31 checking the site 17 clearances 18 connector types 31 M mains power 24 mounting locations 20 positions 20 requirements for 32 22 O operation climatic conditions 13 international standard for 13 m
Nokia MetroSite GSM Base Station, Requirements for Installation and Operation V ventilation 20 W weight BTS 18 mounting rack 38 (38) 18 © Nokia Networks Oy Internal Copy DN9913471 Issue 1 en DRAFT 2 Draft