Instruction Manual

7
Electric Power Generation
0%
5%
10%
15%
20%
25%
30%
0 500 1000 1500 2000 2500 3000
0%
5%
10%
15%
20%
25%
30%
0 500 1000 1500 2000 2500 3000 3500 4000 4500
0%
5%
10%
15%
20%
25%
30%
0 500 1000 1500 2000
0%
5%
10%
15%
20%
25%
30%
0 500 1000 1500 2000
0%
5%
10%
15%
20%
25%
30%
0 500 1000 1500 2000 2500
0%
5%
10%
15%
20%
25%
30%
0 500 1000 1500 2000 2500 3000 3500
B BC CE ED D
B BC CE ED D
B BC CE ED D
TAL 049 - 730 to 1000 kVA - 50 Hz / 915 to 1250 kVA - 60 Hz
Transient voltage variation 480 V - 60 Hz
Phase loading (AREP+) - kVA at P.F. =
0.8
Load shedding (AREP+) - kVA at P.F. =
0.8
Motor starting (AREP+)
Locked rotor kVA at P.F. =
0.6
Voltage dropVoltage riseVoltage drop
Phase loading (SHUNT) - kVA at P.F. =
0.8
Load shedding (SHUNT) - kVA at P.F. =
0.8
Motor starting (SHUNT)
Locked rotor kVA at P.F. =
0.6
Voltage dropVoltage riseVoltage drop
- For a starting P.F. other than 0.6, the starting kVA must be multiplied by K = Sine P.F. / 0.8
- For voltages other than 480V (Y), 277V (Δ), 240V (YY) at 60 Hz, then kVA must be multiplied by (480/U)
2
or (277/U)
2
or (240/U)
2
.
- Transient performance of the PMG option, consult us.