Installation Guide

APPLICATIONS GUIDE:
FITTINGS
Types of Service Comments Pressure Temperature
Compatible with
EPDM Seal
Fluids/Water
Hot and Cold Potable Water 200 PSI 32°F to 250°F
Rainwater/Gray Water
Subject to local codes/authority having
jurisdiction with appropriate precautions
to prevent systems from freezing
Propylene Glycol
200 PSI -20°F to 250°F
Chilled Water
Up to 50% Ethylene Glycol/Propylene
Glycol solution appropriate for the
application temperature range
200 PSI -20°F to 250°F
Hydronic Heating 200 PSI -20°F to 250°F
Cooling Water 200 PSI -20°F to 250°F
Ethanol 200 PSI -20°F to 250°F
Gasses
Compressed Air Less than 25mg/m
3
Oil Content 200 PSI Up to 140°F
Oxygen - O
2
(non-medical) Keep Oil and Fat Free/Non-Liquid O
2
140 PSI Up to 140°F
Nitrogen - N
2
200 PSI Up to 140°F
Argon Welding Use 200 PSI Ambient
Hydrogen - H
2
125 PSI Up to 250°F
Vacuum
Max 29.2 in.
of Mercury-Hg
Up to 140°F
Carbon Dioxide - CO
2
Dry 200 PSI Up to 140°F
Low Pressure Steam 15 PSI Up to 250°F