NIBCO
®
Press System Lead-Free Brass Ball Valves
Handle Markings
PC-FP-600A-LF
Press x Press
2 1/2" - 4"
Size range: 2 1/2” - 4”
Pressure rating: 200 psi non-shock cold working pressure
Maximum pressure / temperature: 200 psi at 200° F
Lead-Free markings: White handle and blue hang tag
MATERIAL LIST
PART SPECIFICATION
1 Handle Steel Plated
2 Handle Cover PVC
3 Handle Lock Nut Steel
4 Stem Brass/Bronze
5 Packing Nut Brass/Bronze
6 Packing PTFE
7 Leak Detection O-ring EPDM - ASTM D2000
8 O-ring, Boss Seal EPDM - ASTM D2000
9 Body End Brass/Bronze
10 Ball Stainless Steel
11 Body Brass/Bronze
12 Ball Seat Seal PTFE
13 Press End Adaptor w/Leak Detection ASTM B75 Alloy C12200
Options:
• Extended lever
• EPDM Seal for Press Ends
PC-FP-600A-LF
Press x Press
2 1/2" - 4"
Features: Press Ends Leak Detection • Two-Piece Body • PTFE Seats • Full Port • Blowout-Proof Stem
Approvals: IAPMO/ANSI Z1157 (IGC-157) • NSF/ANSI-61 & 372 • MSS SP-145 • Conforms to ASME B16.51
†
†Tested to the performance criteria of ASME B16.51
IAPMO/ANSI Z1157: in addition to meeting ICG-157 test requirements, the IAPMO/ANSI Z1157 also requires Press
ends to be fully tested to IAPMO PS-117 performance requirements which includes the following additional tests:
1. Unrestrained Hydrostatic Pressure Test at 20 ºC (68ºF)
2. Unrestrained Hydrostatic Pressure Test at 93 ºC (200ºF)
3. Static Torsion Test for Press Connections
4. Bending Test
5. Vacuum Test
6. Hydraulic Shock (Water Hammer) Test
7. Vibration Test
8. Thermal Cycling Test
9. Alternate Thermal Cycling Test
10. Dynamic Torsion Test for Press Connections
2
Applications: Drinking Water • Domestic Hot & Cold Water • HVAC
(condensors, chilled water, hot water heating) • Isolation and Throttling
(half-open to full-open only) • Connect to Rigid Copper Tubing Manufactured
per ASTM B88, Condition H (hard drawn)
Reference Press System catalog for updated Approved Tool and Jaw
Compatibility Matrix list.
Not intended for steam or gas usage.
DIMENSIONS—WEIGHTS—QUANTITIES
SIZE A B C D E F Weight
In. mm. In. mm. In. mm. In. mm. In. mm. In. mm. In. mm. Lbs. Kg.
2 1/2" 15 13.07 332 8.66 220 4.8 121.9 2.52 64 5.88 149.3 8.81 223.7 9.55 4.33
3 20 13.67 347.2 8.66 220 5.12 130 2.91 73.9 6.71 170.4 10.03 261.6 13.07 5.93
4 25 15.87 403.1 9.61 244.1 5.98 151.9 3.9 99 8.21 208.5 12.53 318.2 26.32 11.94
limited
warranty
2
Dezincification
Resistant
LEAD-FREE: Weighted average lead content ≤ 0.25%
WARNING: This product can expose you to chemicals including lead, which is known to the State of California to cause cancer and birth defects or other