Product Overview
©2016 New Yorker Boiler Company, Inc., Hatfield, PA
info@newyorkerboiler.com
www.newyorkerboiler.com
NYL06161-6/16 5Ms
Ratings & Specifications
A
S
M
E
H
MADE IN
U.S.A.
Safety Relief Valve Pressure, Water – 30 PSI std. ASME “H” stamp. Maximum Allowable Working
Pressure is 50 PSI, Boilers shipped set for natural gas. Product is listed for elevations to 2000’.
Standard Equipment
• Direct vent appliance
• Natural or LP gas
• Stainless steel heat exchanger
• Easy access control panel
• Boiler Control System
– LCD display
– (3) circulator outputs available
– Outdoor reset including outside sensor
– DHW priority
• Variable speed combustion blower
• Gas valve
• Polypropylene condensate trap
• Flow switch, pre-installed
• Supply, return, and flue temperature sensors
• Universal exhaust vent connection
• Differential pressure switch
• Pre-installed hanging bracket and wall mount kit
Optional Equipment
• Kit, CPVC starter and PVC vent terminations:
(2’ P/N: 107039-01) (3” P/N: 107039-02)
12” Min
3”
B
A
26-1/4”
1”
Return Water
Connection 1”
Inside
of Wall
Outside
of Wall
Supply Water
Connection 1”
Drain Valve
Vent Connection
Air Intake Connection
Relief
Valve
Access
Door
Temperature &
Pressure Gauge
Boiler
Control
Display
Junction
Box
Condensate T
rap
Cleanout
Gas Connection 1/2”
Condensate
Connection
Model AFUE%
Input
(MBH)
min-max
DOE
Heating
Capacity
(MBH)
Net AHRI
(MBH)
Vent
Size
(Inches)
GHE080 94.0 16-80 74 64 2 or 3
GHE100 93.3 20-100 92 80 2 or 3
GHE120 94.0 24-120 112 97 3
GHE150 95.0 30-150 142 123 3
GHE180 94.0 36-180 170 148 3
Model A B
GHE080 14” 17-7/16”
GHE100 14” 17-7/16”
GHE120 14” 17-7/16”
GHE150 18-3/4” 19-15/16”
GHE180 18-3/4” 19-15/16”
Typical Venting Configurations
Horizontal 2-pipe
low profile
Horizontal 2-pipe
concentric
Illustrations are for representation only. For complete
venting information, please see Installation manual.
Horizontal 2-pipe
Vertical 2-pipe
Vertical 2-pipe
concentric
Hybrid