User Guide

93
Appendix A: Instructions for Conversion of This Boiler for Use with LP Gas
AllboilerslistedinthismanualarefactoryconguredforuseonNaturalgasataltitudesatorbelow2000feet.Performthesteps
listed in these instructions to convert it for use with LP gas.
1) If not already done, install the boiler in accordance with this manual, following all instructions in Part XI (Start-up and
Check-out) up to Step 10.
2) Set the throttle to its preliminary setting for LP. To do this:
a. Turn the throttle (Figure A.1) clockwise until it stops (several full turns).
b. Turn throttle counter-clockwise the exact number of turns shown in Table A.2.
3) AttempttostarttheboilerusingthelightinginstructionslocatedonPage60.Iftheboilerdoesnotlightonthersttry
for ignition, allow to boiler to make at least four more attempts to light. If boiler still does not light, turn the throttle
counterclockwise in 1/8 turn increments, allowing the boiler to make at least four tries for ignition at each setting, until the
boiler lights.
4) Aftertheburnerlights,forcetheburnertohighrebyenteringtheDiagnosticsMenu,andselectingManualInput,then“HF”
as described in Part XI (start-up and checkout). Allow the boiler to operate for approximately 5 minutes before
takingcombustionreadings.Note:thatafter15minutes,boilerisautomaticallyreleasedfromhighrehold.Theboilerwill
also be released from manual input if the user manually navigates back to the home screen.
5) Performacombustiontest,samplingueproductsfromthetapinthefrontoftheventadaptor.
6) WhiletheburnerisathighreadjustthethrottleasneededtoobtaintheCO
2
settings shown in the Table A.3:
• ToreducetheCO
2
(increase the O
2
) turn the throttle clockwise
• ToincreasetheCO
2
(reduce the O
2
) turn the throttle counter-clockwise
Make adjustments in increments of 1/8 to 1/4 turn and allow the boiler at least a minute to respond to each adjustment before
making another. In general, the CO level will be at its lowest somewhere in the CO
2
range shown in this table. Consult
factory if it is not possible to reduce the CO level below 200PPM air free within the range of CO
2
s shown for the fuel and
altitude at which the boiler is being used.
DANGER
These instructions include a procedure for adjusting the air-fuel mixture on this boiler. This
procedure requires a combustion analyzer to measure the CO
2
and Carbon Monoxide (CO) levels
in ue gas. Adjusting the air-fuel mixture without a proper combustion analyzer could result in
unreliable boiler operation, personal injury, or death due to carbon monoxide poisoning.
WARNING
LP CONVERSIONS - This conversion shall be performed by a qualied service agency in
accordance with the manufacturers instructions and all applicable codes and requirements of the
authority having jurisdiction. If the information in these instructions is not followed exactly, a re, an
explosion or production of carbon monoxide may result causing property damage, personal injury,
or loss of life. The qualied service agency is responsible for proper conversion of this boiler. The
installation is not proper and complete until the operation of the converted appliance is checked as
specied in the instructions below.