User Guide

22
C. Design Requirements Unique to Vertical Venting Systems
Table 7.11 summarizes all vertical twin pipe vent options. In addition to the requirements in Part VII-A, observe the
following design requirements:
1. Permitted Terminals for Vertical Venting
Terminal Option H: Fittings –Ventterminatesinaplainend(couplingforPVC.IntaketerminatesinaPVC180elbow
pointingdown(twosweep90’smaybesubstituted).Observetheclearancesfromtheroof,andnormalsnowlineontheroof,
shown in Figures 7.12 and 7.13.
Use of rodent screens (not supplied) is generally recommended for both terminations. These can be fabricated from 2 x 2
(1/2” mesh) stainless steel screen. They are installed as shown in Figure 7.18.
Terminal Option I: Ipex FGV Concentric Terminal - This terminal is shown in Figure 7.13 and may be used with CPVC/PVC
ventsystems.UseacompatibleroofashingandstormcollarinaccordancewiththeIpexinstructionsforthisterminal.This
terminal is available in various lengths and in both PVC and CPVC. Terminals acceptable for use with these vent options are
as follows:
Ipex PN FGV Concentric Terminal Description
196005 2 x 16” PVC
196105 2 x 28” PVC
196125 2 x 40” PVC
196006 3 x 20” PVC
196106 3 x 32” PVC
196116 3 x 44” PVC
197107 3 x 32” CPVC
197117 3 x 44” CPVC
See Part VII-E of this manual and the Ipex instructions provided with the terminal, for installation details.
Terminal Option J: Diversitech Concentric Terminal - This terminal is shown in Figure 7.13 and may be used with CPVC/
PVC vent systems. See Part VII-E of this manual and the Diversitech instructions provided with the terminal, for installation
details.
2. Vertical Vent and Air Intake Location–Observethefollowingclearancesfromroofmountedterminals:
• Bottomofairintakeopeningmustbeatleast12”abovethenormalsnowlineanticipatedontheroof.
• Exhaustopeningmustbeatleast2ftaboveanyportionoftherooforstructurelocatedwithinhorizontallywithin10ft.
• ForterminaloptionH,maintainatleast12”ofverticalseparationbetweentheexhaustandintakeopeningasshownin
Figure 7.12.
NOTICE
Vertical venting and combustion air roof penetrations (where applicable) require the use of roof
ashing and storm collar, which are not supplied with the boiler, to prevent moisture from entering the
structure.