reset by pressing the reset button located
on the primary control. If the flame is lost
while the burner is firing, the primary control
shuts down the burner, enters a 60 second
recycle delay, and repeats the ignition
sequence. If after three (3) trials for ignition,
flame is not detected, primary control will
enter into restricted mode. Restricted mode
is reset by holding down the reset button for
15 seconds.
3. Using Boiler Control
The Boiler Control is located on front of boiler.
The Boiler Control display, along with Up
ñ,
Down ò, and “I” keys may be used to view
boiler operating status (Figure 31).
4. Viewing the Operating Mode Options
In operating mode the user may view (but not
change) boiler operating status, settings and
troubleshooting information. To view Boiler
Control display information:
Press and release the “I” key on the Boiler
Control to change from one parameter to
the next. Each setting will alternately flash
between the relevant display code and its
corresponding value.
Figure 31: Boiler Control
Key Function & Orientation
For example, when the “
I” key is pressed
on the Boiler Control until “bt” is displayed,
it will then flash a three digit number (such
as “0”) followed by either “F” (or “C”). This
indicates that the boiler water temperature is
180°F. Other operating parameters display the
information in a similar fashion.
Please note that in operating mode to hold the
display on the value the user can press and
hold either the Up ñ or Down ò keys and the
value will be continuously shown. This may be
helpful in watching a value “live”.
5. Changing the Adjustable Parameters
To adjust parameters such as the High Limit
Setpoint and High Limit Differential:
a. Using the Boiler Control display, access
the adjustment mode by pressing and
holding the Up ñ, Down ò, and “I” keys
simultaneously for three (3) seconds.
This procedure is intended to discourage
unauthorized changes or accidental
changes to limit settings.
b. Press the "
I" key to display available
Adjustment Mode options. Select an option.
Operating Mode Options
t
Status Numbers:
Standby
Running
Self Test
bt
Boiler Temperature
P
Operating Setpoint (Outdoor Reset)
HL
High Limit Setting
HdF
High Limit Differential
LL
Low Limit Setpoint (warm start only)
LdF
Low Limit Differential (warm start only)
hr
Heat Request Status
dh
DHW Request Status
Err
Boiler Error
Cold Start Boiler Control
Adjustment Mode Options
HL_
140-240°F Adjust High Limit Setting
HdF
10-30°F Adjust High Limit Differential
ZC_ dh, ZR or ELL
ZC and ZR Terminal Function
Or_ 0-10 minutes
Pump Overrun Time
PP_ 2-20 minutes
Pump Pre-purge Time
t_ 140 - 180°F
Start Temperature
Pt_ On or Off
Priority Time
f-C F or C
Select degrees F or C Mode
bac
Back to Operating Mode
Warm Start Boiler Control
Adjustment Mode Options
HL_
140-240°F Adjust High Limit Setting
LL_
110-220°F Adjust Low Limit Setting
Ldf
10-25°F
Adjust Low Limit Differential
Setting
ZC_ ZR or dh
ZC and ZR Terminal Function
Or_
0-10 minutes Pump Overrun Time
PP_
0-20 minutes Pump Pre-purge Time
t_
140 - 180°F Start Temperature
Pt_ On or Off
Priority Time
f-C F or C
Select degrees F or C Mode
bac
Back to Operating Mode