User Guide

23
103876-08 - 1/19
CL
Installation & Service Manual
Figure 18: Proper and Improper Locations of Draft Regulator
used. Only approved clay liners or listed
chimney lining systems shall be used as
specified in NFPA 31 or CSA B139.
c. Abandoned Openings – Openings through
the chimney wall that are no longer used
shall be sealed in accordance to NFPA 211.
Often abandoned openings are improperly
sealed and usually covered by a gypsum
wall covering.
d. Clean Chimney – Chimney shall be free of
all loose debris.
5. Draft Regulator – a draft regulator must be
used with this appliance. Refer to Figures 17
and 18.
Chimney Connector
DANGER
The chimney and connector shall
be inspected annually for signs of debris and
corrosion. Loose mortar at the base of the
chimney may be a sign of condensate damage
to the chimney. A chimney professional shall
be contacted immediately to examine the
damage and recommend a solution. Long
Figure 17: Recommended Smokepipe Arrangement
and Chimney Requirements
3 Installation Instructions (continued)