RIELLO 40 SERIES OIL BURNER PART NUMBERS
FOR CL SERIES BOILERS
TABLE 14B: RIELLO BURNER SPECIFICATIONS
Boiler Model
Firing
Rate
GPM
Burner
Model
Settings Nozzle
3
Pump
Pressure
Combustion
Head
Insertion
Depth
Air Gate Turbulator
GPH x Angle
Type
2
Shipped
CL3-105 0.75 40F5 2.60 0
0.60 x 60A
(Delavan)
Installed 150
SBT 6.0” 2-3/8”
CL3-140 1.00 40F5 2.85 2
0.85 x 60W
(Delavan)
Installed 150
CL4-126 0.90 40F5 2.25 0
0.75 x 60B
(Delavan)
Installed 145 SBT 6.0" 2-1/4"
CL4-175 1.25 40F5 4 4
1.00 x 60A
(Delavan)
Installed 150 SBT 6.0” 2-3/8”
CL4-210 1.50 40F10 3 1
1.25 x 60B
(Delavan)
Installed 150 SBT 5.0” 2-1/2”
CL5-168 1.20 40F5 2.9 0
1.00 x 80B
(Delavan)
Installed 145 Set 6.0" 2-1/4"
CL5-245 1.75
40F10
3 1.5
1.35 x 45B
(Delavan)
p Loose
150
SBT 5.0” 2-1/2”
p CL5-280
2.00 3.8 2
1.65 x 45B
(Delavan)
Installed 150
2
Nozzle(s) for alternate boiler model ring rate(s) are shipped loose in bag attached to the
burner designated by corresponding symbol, i.e. (p) = CL3-105.
3
Single stage fuel pump is standard, two stage fuel pump is optional. Burner manufacturer has preset
single stage fuel pump to settings shown in table above
NOTE: When ordering parts always give the serial and model numbers shown on the boiler and burner.
Refer to Models F3 & F5 Installation Manual, Riello 40 Series Residential Oil Burners (C6501010) or Model F10
Installation Manual, Riello 40 Series Residential Oil Burners (2902554) for an exploded view of the burner and a list of spare
parts.
For replacement Riello oil burner parts, contact your wholesaler or the burner manufacturer:
Riello Corporation of America
35 Pond Park Road
Hingham, Massachusetts 02043
Telephone: (617) 749-8292
Facsimile: (617) 740-2069
Toll Free: (outside Massachusetts)
(800) 992-7637
Riello Canada Inc.
2165 Meadowpine Blvd.
Mississauga, Ontario L5N 6H6
Telephone: (905) 542-0303
Facsimile: (905) 542-1525
Toll Free: (800) 387-3898
XI: BURNER SPECIFICATIONS (continued)