User Guide
61
103876-08 - 1/19
CL
Installation & Service Manual
Table 14A: Beckett Afg Burner Specifications
Beckett AFG
Boiler Series
Firing Rate
GPH
Settings Nozzle
3
Pump
Pressure
Head
(Setting)
Air
Shutter
Air
Band
GPH x Angle Type
4
2
Shipped
1
CL3-091
0.65
L1
8 0 0.55 x 70B
p Loose
140CL3-105 0.75 10 2 0.65 x 60B (Hago)
p Loose
p CL3-140
1.00 5 2 0.85 x 60B (Hago) Installed
CL4-126 0.90 L1 7 0 0.75 x 60B Installed 140
CL4-175 1.25
V1(0)
10 0.5 1.00 x 60B (Hago)
Loose
140
CL4-210
1.50 10 6 1.25 x 60B (Hago) Installed
CL5-168 1.20 V1(0) 8 1 0.90 x 60B (Hago)
Loose
175CL5-245 1.75 V1(3) 6 6 1.35 x 45B (Hago)
Loose
CL5-280
2.00 V1(4) 8 4 1.50 x 45B (Hago) Installed
1
Beckett low firing rate baffle required on CL3-091 (0.65 GPH) application only; shipped loose with nozzle.
2
Nozzle(s) for alternate boiler series firing rate(s) are shipped loose in bag attached to the burner designated by
corresponding symbol, i.e. (p) = CL3-140.
3
Single stage fuel pump is standard, two stage fuel pump is optional. Burner manufacturer has preset
single stage fuel pump to settings shown in table above.
4
All burners utilize Delavan nozzle unless otherwise specified.
11 Burner Specifications