Install Instructions

62
103876-08 - 1/19
CL Installation & Service Manual
RIELLO 40 SERIES OIL BURNER PART NUMBERS FOR CL SERIES BOILERS
Table 14B: Riello Burner Specifications
Boiler
Series
Firing
Rate
GPM
Burner
Model
Settings Nozzle
Pump
Pressure
Air Gate Turbulator GPH x Angle Type
4
2
Shipped
CL3-105 0.75
40F5
2.60 0 0.60 x 60A Installed
150
CL3-140 1.00 2.85 2 0.85 x 60W Loose
CL4-126 0.90 40F5 2.25 0 0.75 x 60B Installed 150
CL4-175 1.25 40F5 4 4 1.00 x 60A Installed 150
CL4-210 1.50 40F5 3 1 1.25 x 60B Installed 150
CL5-168 1.20 40F5 2.9 0 1.00 x 80B Installed 150
CL5-245 1.75
40F10
3 1.5 1.35 x 45B
Loose
150
CL5-280
2.00 3.8 2 1.65 x 45B Installed
2
Nozzle(s) for alternate boiler series firing rate(s) are shipped loose in bag attached to the
burner designated by corresponding symbol, i..e. () = CL5-280.
4
All burners utilize Delavan nozzle unless otherwise specified.
NOTE: When ordering parts always give the serial and model numbers shown on the boiler and burner.
Refer to Models F3 & F5 Installation Manual, Riello 40 Series Residential Oil Burners (C6501010) or Model F10
Installation Manual, Riello 40 Series Residential Oil Burners (2902554) for an exploded view of the burner and a
list of spare parts.
For replacement Riello oil burner parts, contact your wholesaler or the burner manufacturer:
Riello Corporation of America
35 Pond Park Road
Hingham, Massachusetts 02043
Telephone: (781) 749-8292
Toll Free: (outside Massachusetts)
(800) 474-3556
Riello Canada Inc.
2165 Meadowpine Blvd.
Mississauga, Ontario L5N 6H6
Telephone: (905) 542-0303
Facsimile: (905) 542-1525
Toll Free: (800) 387-3898
11 Burner Specifications (continued)