User Guide
©2014 New Yorker Boiler Company, Inc., Hatfield, PA
info@newyorkerboiler.com
www.newyorkerboiler.com
NYL02141-5Ms
Ratings&Specifications
Model
Input
Gas
(MBH)
DOEHeating
Capacity
(MBH)
NetAHRI
Steam
(MBH)
Steam
Sq.Ft. AFUE%
CGS30C 69 56 42 175 81.9
CGS40C 103 84 63 263 82.0
CGS50C 138 113 85 354 82.0
CGS60C 172 142 107 446 82.1
CGS70C 207 171 128 533 82.1
CGS80C 241 199 149 621 82.2
Model
Number
of
Sections
Dimensions(inches)
Approximate
ShipWeight
(lbs.)A B C
FlueCollar
Diameter
CGS30C 3 12-3/4 28 40-7/16 4 350
CGS40C 4 16 28 40-7/16 5 420
CGS50C 5 19-1/4 28 40-7/16 6 485
CGS60C 6 22-1/2 28 40-7/16 6 555
CGS70C 7 25-3/4 30 40-7/16 7 620
CGS80C 8 29 30 40-7/16 7 690
Standard Features
• Fullypackaged
• Insulatedjacket
• Pressurelimit
• 15PSIsafetyvalve
• Honeywellgasvalve
• Probe-typeLWCO
• Steampressuregauge
• Built-indraftdiverter
• Flamerolloutswitch
• Blockedventswitch
• Ventdamper
• Drainvalve
A
S
M
E
H
MADE IN
U.S.A.
Ratingsshownareforinstallationsatsealevelandelevationsupto2,000feet.Forhigher
elevations,reduceratings4%foreach1,000feetabovesealevel.
The Net AHRI Steam Ratings shown are based on a piping and pickup allowance of 1.333.
Themanufacturershouldbeconsultedbeforeselectingaboilerforinstallationshavingunusualpiping
andpickuprequirements,suchasintermittentsystemoperation,extensivepipingsystems,etc.


