Product Overview

38
WARNING
SOOTDEPOSITSINTHEFLUEPASSAGESAREASIGNTHATTHEBOILERMAYBEOPERATING
AT HIGH CARBON MONOXIDE (CO) LEVELS. AFTER CLEANING THE BOILER OF SOOT DEPOSITS,
CHECKTHECOLEVELINTHEFLUEGASTOINSURETHATTHEBOILERISOPERATINGPROPERLY.
 IfitisnecessarytocheckCO,useacombustionanalyzer,orotherinstrumentwhichisdesignedtomeasureCOinue
gas.ACO“sniffer”designedfortestingCOlevelsinambientaircannotbeusedtocheckboilercombustion.Takeaue
gassamplebyinsertingasampleprobethroughthedraftdiverteropeningandintotheuecollectorsothatthesampleis
takenintheareadirectlyovertheheatexchanger.Donottakeasampleuntiltheboilerhasbeenringforatleastvemin-
utes.
A normal CO reading for a CGS-C series boiler is less than 50ppm (0.005%). A reading of more than 100ppm (0.01%)
is indicative of a combustion problem.
Some causes of excessive CO include:
• Incorrectlysizedmainburneroriceforthealtitudeatwhichboilerisinstalled
• Crookedorout-of-roundoriceholes(neverattempttodrilloriceforthisboilerintheeld)
• Partiallypluggeduepassages
• Improper manifold pressure
• Foreign material in burner venturis or burner ports
• Leakinsealbetweenuecollectorandheatexchanger
• Inadequate supply of combustion air
XII. Service Instructions (continued)