User Guide

3
110118-01 12/19
CG-F
Installation, Operating & Service Manual
Table 1-1: Dimensions and Connections
Boiler
Model
Depth Width Height
Supply NPT
(inch)
Return NPT
(inch)
Vent
(inch)
Gas NPT
(inch)
Relief Valve
NPT (inch)
Drain
NPT (inch)
CG30F 32 14 40 4 ½ ¾ ¾
CG40F 32 16 40 5 ½ ¾ ¾
CG50F 32 19 40 6 ½ ¾ ¾
CG60F 32 22 40 6 ½ ¾ ¾
CG70F 32 25 40 7 ¾ ¾ ¾
CG80F 32 28 40 7 ¾ ¾ ¾
CG90F 32 31 40 8 ¾ ¾ ¾
Electrical Requirements: 120VAC, 60 Hz, 1-ph, Less than 12A
Maximum Allowable Working Pressure - 50 psi. Boiler shipped from factory with a 30 psi relief valve.
Boiler
Model
Input (MBH)
(1)
Shipping Weight
(lbs)
Empty Weight
(lbs)
Water Content
(gal)
CG30F 70 254 180 2
CG40F 105 304 231 3
CG50F 140 357 284 4
CG60F 175 405 332 5
CG70F 210 462 382 6
CG80F 245 518 438 7
CG90F 280 564 484 8
Table 1-2: Inputs, Weights and Volumes
(1)
Input ratings can be used for elevations up to 2000 ft. Refer to System Start-up and Checkout Sections for
elevations 2000 ft. or higher.
1 Dimensional and Physical Data