Install Instructions
14
VI. Electrical
A. General. Install wiring and ground boiler in accordance
with requirements of authority having jurisdiction, or
in absence of such requirements the National Electrical
Code, ANSI/NFPA 70.
B. Install thermostat. Locate on inside wall
approximately 4 feet above oor. Do not install on
outside wall, near replace, or where inuenced by
drafts or restricted air ow, hot or cold water pipes,
lighting xtures, television, or sunlight. Allow free air
movement by avoiding placement of furniture near
thermostat.
C. Wire thermostat. Provide Class II circuit between
thermostat and boiler. Set thermostat heat anticipator to
0.3 amps. See Figure 14.
If system tends to overheat above thermostat's
temperature setting, reduce heat anticipator setting by
0.1 or 0.2 amps. If system tends to shortcycle without
reaching desired room temperature, increase heat
anticipator setting by 0.1 or 0.2 amps.
D. New Yorker Link SL™ indirect water heater (if
used). See Figures 11 and 12. Also refer to the New
Yorker Link SL™ Indirect Water Heater Installation,
Operating and Service Instructions.
F. Wire boiler. Boiler is rated for 120 VAC, 60 hertz,
less than 15 amperes. A separate electrical circuit
must be run from the main electrical service with an
over-current device/disconnect in the circuit. A service
switch is recommended and may be required by some
local jurisdictions. Connect to black and white wires
and green ground screw. See Figures 11 and 12.
E. For installations using zone valves provide separate
transformer for zone valve wiring. Consult zone valve
manufacturer for assistance. See Figure 13.
CAUTION
This boiler contains controls which may cause
the boiler to shut down and not restart without
service. If damage due to frozen pipes is a
possibility, the heating system should not be
left unattended in cold weather; or appropriate
safeguards and alarms should be installed on the
heating system to prevent damage if the boiler is
inoperative.










