Product Overview
©2020 New Yorker Boiler Company, Inc., Lancaster, PA
info@newyorkerboiler.com
www.newyorkerboiler.com
NYL02161-6/20 3Ms
Ratings & Specifications
A
S
M
E
H
MADE IN
U.S.A.
Model
Dimensions (inches)
Vent Size
Diamater
(in.)
Approx.
Shipping
wt. (lbs.)
Width
“W” Height
Depth
(total) Supply Return
Gas
Valve
Relief
Valve
CG30F 14 40 33-1/4 1-1/4 1-1/4 1/2 3/4 4 254
CG40F 16 40 33-1/4 1-1/4 1-1/4 1/2 3/4 5 304
CG50F 19 40 33-1/4 1-1/4 1-1/4 1/2 3/4 6 357
CG60F 22 40 33-1/4 1-1/4 1-1/4 1/2 3/4 6 405
CG70F 25 40 33-1/4 1-1/4 1-1/4 3/4 3/4 7 462
CG80F 28 40 33-1/4 1-1/4 1-1/4 3/4 3/4 7 518
CG90F 31 40 33-1/4 1-1/4 1-1/4 3/4 3/4 8 564
All models certified for use from sea level to 10,000 feet in elevation.
Input & outputs are reduced by 4% per 1,000 feet above sea level for elevations above 2,000 ft.
Boilers are shipped with 30 psi safety relief valves, MAWP is 50 psi.
NOTES:
1. Minimal radial
distance around vent
pipe and breeching
for single-wall metal
pipe vent connector,
otherwise follow
vent connector
manufacturer’s
recommended
clearances.
2. Add height required
to maintain 6”
clearance from all
vent components.
Standard Equipment
• Insulated steel jacket
• Integral draft diverter, damper and connector
included
• Heavy gauge 1” base insulation
• Integrated boiler control – simple, self-diagnostic,
with 3-digit readout for status
• Step-opening redundant gas valve
• 130°F minimum return temperature rating
• Spark ignition with continuous retry
• User-friendly wiring with 120V J-box
• Circulator – choice of Taco or Grundfos
• Cast iron section assembly
• Resettable blocked vent switch
• Boiler drain valve
• Cast iron supply manifold with safety relief valve
tapping
• Stainless steel burners
Supply
Electrical
Gas
Return
Floor Line
6” Min (see Note 1)
13”
25”
31”
0”
35”
6”
0”
16”
18”
24”
27”
40”
63”
Floor Line
23” (see Note 2)
40”
4”
W
1”
26-3/4”
33-1/4”
Supply
Electrical
Gas
Return
Floor Line
6” Min (see Note 1)
13”
25”
31”
0”
35”
6”
0”
16”
18”
24”
27”
40”
63”
Floor Line
23” (see Note 2)
40”
4”
W
1”
26-3/4”
33-1/4”
Model
Input
(MBH)
DOE Heating
Capacity
(MBH)
Net AHRI
Rating, Water
(MBH) AFUE%
CG30F 70 59 51 84.0
CG40F 105 88 77 84.0
CG50F 140 117 102 84.0
CG60F 175 146 127 84.0
CG70F 210 176 153 84.0
CG80F 245 205 178 84.0
CG90F 280 234 203 84.0