Manual
20
Figure 18: 40mm Main Burner Flame
D. Check Gas Input to Boiler
rst two items in order to utilize the formula
below. The gas meter should then be clocked
for three (3) minutes with stop watch and
substituting the appropriate values in the formula
below, determine what the gas ow should be in
this 3 minute period to give the input shown on
the Rating Label:
Gas Input cu. ft. __________Btuh Input_________
per 3 min. = Heating Value Multiplier from
of Gas X Table 5
(Btu / cu. ft.)
E. Check Main Burner Flame. See Figure 18 or 18a.
Flame should have a clearly dened inner cone with no
yellow tipping. Orange-yellow streaks caused by dust
should not be confused with true yellow tipping.
1. Input Rate and Maximum Inlet Pressure shown on
Rating Label must not be exceeded. Inlet pressure
must not be lower than minimum inlet pressure
shown on Rating Label.
2. All Rate checks and all adjustments are to be made
while boiler is ring - all other appliances connected
to the same meter as the boiler must be off.
3. With boiler off, water Manometer or water
column gauge should be connected to a shut-off
cock installed in the 1/8" outlet pressure tap in
the gas valve (See Figure 14). By installing gas
cock upstream of manometer, gas pressure can be
introduced gradually - without shut-off cock; surge
of pressure when boiler is turned on, could blow
liquid out of manometer. Replace plug in gas valve
when rate check is nished.
4. LP Gas Input:
Adjust Regulator on Gas Valve so that manifold
pressure is 10 inches water column. Turning
Regulator Adjusting Screw Clockwise increases
pressure. Counterclockwise rotation decreases
pressure.
5. Natural Gas Input
a. Approx. Input - Adjust regulator on Gas Valve
so that manifold pressure is three and a half (3½)
inches water column (three inches water column
for high altitude). Turning Regulator Adjusting
Screw Clockwise increases pressure, Counter-
clockwise rotation decreases pressure. If more
accurate check on input is necessary see (b) .
For minor input changes readjust Regulator Gas
Valve to increase or decrease manifold pressure
to obtain corresponding increase manifold
pressure more than 0.3" of water to obtain rated
input, remove orices and drill one size larger.
Reinstall and recheck input rate.
b. Additional Check on Input - Since input is a
function of heating value, specic gravity, and
volume of gas ow contact your utility for the
Figure 18a: 1 Inch Main Burner Flame
NOTICE
CG-C boilers built for installation at altitudes greater
than 2,000 feet above sea level have been specially
oriced to reduce gas input rate 4 percent per 1,000
feet above sea level per the National Fuel Gas Code,
NFPA 54/ANSI Z223.1. High altitude boiler models
are identiable by the third digit in the model number
sufx on the rating label:
CG_OC- _ _ 2: less than 2000 ft. elevation
CG_OC- _ _ 5: 2000 to 5000 ft. elevation
CAUTION
Avoid operating this boiler in an environment
where saw dust, loose insulation bers, dry wall
dust, etc. are present. If boiler is operated under
these conditions, the burner interior and ports
must be cleaned and inspected daily to insure
proper operation.










