User Manual

Slide bushing ( 1 ) and chuck ( 2) onto the cable end.
If cable O.D.:
Less 15 mm please use reduction piece (3).
Prepare cable as shown.
Consider excessive length of PE conductor for
slackening.
Strip the wires.
Caution:
The conductor cross section for the rated current is
6mm2 (10 AWG). In the exceptional case that the
conductor cross section area is smaller as the rated
cross section the maximum current load carrying
capacity has to be assessed according to the limit of
the conductor. Also it is advised to use wire end
sleeves for smaller cross section areas.
ASSEMBLY INSTRUCTIONS
|
CABLE CONNECTOR
A
B
A
[0.354"]
9 mm
FEATURES
250 Vac, 32 Amp (at ambient temperatures up to 35°C) / 30 Amp for cUR
Cable O.D. 17 mm (general range: 8.0 to 20.0 mm)
2
Wiring: Cable Connector: Screw-type terminals for stranded wires 6.0 mm (AWG 10)
2
Chassis Connector: Screw-type terminals for wires 6.0 mm (AWG 10)
·
·
·
IMPORTANT SAFETY INSTRUCTION
Caution: Connector without breaking capacity acc. IEC 61984 - must not be engaged or
disengaged when under load or live.
Attention: Ne pas utiliser pour couper le courant.
Insert wires into terminals L, N, PE and tighten.
ATTENTION: Max torque 150 cNm
Wiring (left):
C
C
1
2
3
1.
2.
SAFETY & ASSEMBLY INSTRUCTION
powerCON HC Locking 2P+PE AC appliance coupler
®
|
L
Black
N
White
PE
Green
Page 1
R
25 mm 15 mm
[0.985”] [0.590”]