Submittal Sheet

MOUNTING OPTIONS
It is recommended that Neutra-Safe condensate neutralizers be installed as close as possible to the outlet
of the condensate trap.
Condensate neutralizer may be installed on level ground or mounting brackets (not provided).
Model CN6T has screw inserts in its base which can be used if needed.
Neutra-Safe condensate neutralizers may be installed on or above the oor so long as a pitch of ¼" per foot
is maintained between the neutralizer outlet and the drain or pump.
It is recommended that unions be installed to facilitate maintenance of the condensate neutralizer
INSTALLATION
1. Neutra-Safe CN6T condensate neutralizers are provided with 1" tappings at either end to accommodate ttings of choice.
2. If using PVC pipe, apply Teon tape to the threads of PVC socket adaptors and attach to neutralizer. Do not over tighten.
3 Identify suitable location for assembled condensate neutralizer. Observe direction of ow as indicated on neutralizer.
4. PVC unions should be secured at either end of the neutralizer.
5. Prime and glue PVC pipe to ttings.
Note: If using exible tubing, be sure to use hose clamps at barb ttings.
Note: PVC pipe is the preferred method for piping condensate drain lines.
6. Route PVC pipe or tubing to drain or pump, maintaining a pitch of ¼" per foot.
7. Fill condensate trap with water until ow is established through neutralizer.
8. Observe neutralizer during boiler operation to ensure unrestricted condensate ow.
MAINTENANCE
1. All service items should be undertaken by a qualied professional.
2. Visually inspect unit for signs of leaking or damage.
3. Neutralizer media should be replaced at least once a year or when pH falls below local regulations.
Neutralizer efciency can only be determined by measuring pH level of condensate outow.
4. Refer to chart below for appropriate rell kit.
Neutra-Safe
®
Replacement Media Kit
Model # Recharge Kit
CN6T 6TKRCK-S
5. Disconnect condensate line from both the inlet and the outlet of the neutralizer.
6. Unscrew cap and remove spent neutralizer media. Rinse empty neutralizer with water.
7. Add replacement media and replace cap.
8. Reattach neutralizer to condensate line and prime ue gas trap with a minimum of 1 gallon of water.
9. Observe neutralizer during boiler operation to ensure unrestricted condensate ow.
NS Tank IOM 9-2020
LIMITED WARRANTY
All Neutra-Safe products are warranted against defects in materials and workmanship for ONE YEAR.
The warranty does NOT cover issues that result from misuse, improper installation, and/or failure to replace the media.