User Guide
Neutra-Safe
®
Condensate Neutralizer
Tray Style Model CN5TR
Installation, Operation and Maintenance Manual
Neutrasafe Corporation
neutrasafe.com
421 Page Street, Suite 1
Stoughton, MA 02072
WARNING
• Neutra-Safe
®
condensate neutralizers should only be installed by a qualied professional.
• Read all instructions before installing. Perform steps in the order given. Failure to comply could result in substantial property damage,
severe personal injury, or death.
• Do not allow ue gases to vent through condensate neutralizer. All condensate drain lines must have a gas trap
before entering the neutralization unit. Failure to comply could result in substantial property damage, severe
personal injury or death.
• Neutra-Safe neutralizers should only be connected to a condensate outlet that is installed per the appliance manufacturer’s instructions.
Failure to comply could result in substantial property damage, severe personal injury, or death.
IMPORTANT
• All piping should be in accordance with relevant building and mechanical codes, as well as any local,
state or federal regulations.
• Do not connect more than one appliance to each neutralizer.
• Neutralizer should be installed below all traps and condensate outlets.
• Neutra-Safe CN5TR condensate neutralizer should always be mounted on a level surface. It is also recommended that the installer
maintain a pitch of ¼" per foot between the condensate neutralizer outlet and the pump or drain.
• Do not use pipe dope on threaded ttings—use only Teon tape.
• Neutra-Safe condensate neutralizers may NOT be installed in the vertical position.
• It is recommended that the neutralizer be installed before the condensate pump.
• All condensate traps should be primed before commencing operation of the appliance.
• Neutra-Safe condensate neutralizer media should be replaced at least once a year or when pH falls below local regulations.
5,000,000 BTU/h