User Guide

Neutra-Safe
®
Condensate Neutralizer
Tray Style Model CN5TR
Installation, Operation and Maintenance Manual
Neutrasafe Corporation
neutrasafe.com
421 Page Street, Suite 1
Stoughton, MA 02072
WARNING
• Neutra-Safe
®
condensate neutralizers should only be installed by a qualied professional.
Read all instructions before installing. Perform steps in the order given. Failure to comply could result in substantial property damage,
severe personal injury, or death.
Do not allow ue gases to vent through condensate neutralizer. All condensate drain lines must have a gas trap
before entering the neutralization unit. Failure to comply could result in substantial property damage, severe
personal injury or death.
Neutra-Safe neutralizers should only be connected to a condensate outlet that is installed per the appliance manufacturer’s instructions.
Failure to comply could result in substantial property damage, severe personal injury, or death.
IMPORTANT
All piping should be in accordance with relevant building and mechanical codes, as well as any local,
state or federal regulations.
Do not connect more than one appliance to each neutralizer.
Neutralizer should be installed below all traps and condensate outlets.
Neutra-Safe CN5TR condensate neutralizer should always be mounted on a level surface. It is also recommended that the installer
maintain a pitch of ¼" per foot between the condensate neutralizer outlet and the pump or drain.
Do not use pipe dope on threaded ttings—use only Teon tape.
Neutra-Safe condensate neutralizers may NOT be installed in the vertical position.
It is recommended that the neutralizer be installed before the condensate pump.
All condensate traps should be primed before commencing operation of the appliance.
Neutra-Safe condensate neutralizer media should be replaced at least once a year or when pH falls below local regulations.
5,000,000 BTU/h