Installation Instructions

22 © 2015 UTC Fire & Security Americas Corporation, Inc. All rights reserved.
Close Schedule: On if output should only activate between the closing and
opening time.
Schedule Times: Sets the Opening / Closing hours and minutes (24 hour format)
and the days of the week the event must occur in before the output will activate.
Output Schedule Days: Is used to select the days the event must occur within
before the output will activate.
IP Reporting
Serial Number: This is the serial number for the NX-595E. This field is not editable.
Use PSTN for Failover: If IP reporting fails, switch to the alarm panel dialer for
backup communication path (only valid when PSTN line is connected).
Note: In order to prevent dual reporting (IP and PSTN) when selecting the Use
PSTN for Failover option, it will be necessary to change the panel configuration.
This is accomplished by programming Location 4, segments 1 and 2 in the NetworX
panel for Phone 1 Events Reported. Disable options 1-6 and 8 (option 7 must
remain on) for Segment 1. Disable all options (1-8) for Location 4, Segment 2 also.
If using phone 2 and 3 (locations 10 and 16) respectively, disable the
corresponding options for segments 1 and 2 as described above.