Installation Instructions
18 © 2015 UTC Fire & Security Americas Corporation, Inc. All rights reserved.
Feature Setup
Enable Zone Doubling: Allow the two onboard zones to double to four zones (not
available on NX-4 panels). These zones cannot be used for 2-wire smoke
detectors.
Start Zone: Used to enter the starting zone number of the additional zones on the
NX-595E. Select from the drop down menu.
Installer Name: Default installer name is installer and is case sensitive. This is
the username to sign in via a web browser or the UltraSync application.
Service Number: The system service number will be announced at NX-181xx
Voice keypads when a system fault is present. Your customer service telephone
number is the recommended setting.
GMT Offset Hours/Minutes: Sets local GMT (Greenwich Mean Time).
DST Start / End month: Selects the month daylight savings begins and ends for
the particular installation region.
DST Start / End week: – Selects which Sunday daylight savings begins and ends
for the particular installation region.
Firmware, Hardware, Web version, Voice and Language: Displays the current
versions loaded on the connected NX-595E.
Zone
Lower
Zone
Higher
Zone
Single EOL resistors
3.3K
N/A
N/A
Zone Doubled EOL resistors
N/A
3.7K
6.9K