User Manual
Table Of Contents
7
(2) Read device configuration parameters
Downlink: 0299000000000000000000
The device returns:
8299003C003C0064006400 (current device configuration parameters)
Report Current and Illuminance Data Example
R718NL3
0x99
0x01
Battery
(1Byte, unit:0.1V)
Current1
(2Bytes, Unit:1ma)
Current2
(2Bytes, Unit:1ma)
Current3
(2Bytes, Unit:1ma)
Mulitplier1 (1Byte),
the real current1
should convert with
Current* Mulitplier
0x02
Battery (1Byte,
unit:0.1V)
Mulitplier2(1Byte),
the real current2
should convert with
Current* Mulitplier
Mulitplier3 (1Byte),
the real current3
should convert with
Current* Mulitplier
Illuminance
(4Bytes, Unit:1Lux)
Reserved
(1Bytes, fixed 0x00)
FPort 6 Report Data (1): 01990124 03E8 03E8 03E8 01
(2): 01990124 01 01 00000003 00
Current1=Current1*Mulitplier1、Current2=Current2*Mulitplier2、Current3=Current3*Mulitplier3
When illuminance less than 3 lux, the reported value is 3 lux.
Example for MinTime/MaxTime logic
Example#1 based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V
MaxTime MaxTime
Sleeping(MinTime)
Sleeping(MinTime)
Note: MaxTime=MinTime. Data will only be report according to MaxTime (MinTime) duration regardless BatteryVoltageChange
value.
Wake up and collects data
REPORTS 3.6V
Wakes up and collects data
REPORTS 3.6V
Wakes up and collects data
REPORTS 3.6V