User Manual

6
Data report configuration and sending period are as following:
Example of Report configuration
FPort0x07
Bytes 1 Byte 1 Byte Var(Fix =9 Bytes)
CmdID
DeviceTy
pe
NetvoxPayLoadData
CmdID– 1 byte
DeviceType1 byte Device Type of Device
NetvoxPayLoadDatavar bytes (Max=9bytes)
(1) Configure report parameters MinTime = 1min, MaxTime = 1min, CurrentChange = 100mA, IlluminanceChange = 100Lux
Downlink: 0199003C003C0064006400
The device returns:
8199000000000000000000 (Configuration succeeded)
8199010000000000000000 (Configuration failed)
Min. Interval
(Unit:second)
Max. Interval
(Unit:second)
Reportable Change
Current Change
Reportable Change
Current Change
Reportable Change
Any number between
30~65535
Any number between
Min.~65535
Can not be 0.
Report
per Min. Interval
Report
per Max. Interval
Description Device
Cmd
ID
Device
Type
NetvoxPayLoadData
ConfigReport
Req
R718NL3
0x01
0x99
MinTime
(2bytes
Unit:s)
MaxTime
(2bytes
Unit:s)
CurrentChange
(2byte
Unit:1mA)
Illuminancechange
(2bytes Unit:1Lux)
Reserved
(1Bytes, Fixed
0x00)
ConfigReport
Rsp
0x81
Status
(0x00_success)
Reserved
(8Bytes,Fixed 0x00)
ReadConfig
ReportReq
0x02
Reserved
(9Bytes,Fixed 0x00)
ReadConfig
ReportRsp
0x82
MinTime
(2bytes
Unit:s)
MaxTime
(2bytes
Unit:s)
CurrentChange
(2byte
Unit:1mA)
Illuminancechange
(2bytes Unit:1Lux)
Reserved
(1Bytes, Fixed
0x00)