Tus neeg siv phau ntawv
Table Of Contents
7
5.2 Example of Report configuration
FPort:0x07
Bytes 1 1 Var(Fix =9 Bytes)
CmdID DeviceType NetvoxPayLoadData
CmdID– 1 byte
DeviceType– 1 byte – Device Type of Device
NetvoxPayLoadData– var bytes (Max=9bytes)
(1) Configure device parameters MinTime = 1min, MaxTime = 1min, BatteryChange = 0.1v, Temperaturechange = 10℃
Downlink: 0114003C003C0100640000
Device returns:
8114000000000000000000 (configuration successful)
8114010000000000000000 (configuration failed)
(2) Read device parameters
Downlink: 0214000000000000000000
Device returns:
8214003C003C0100640000 (current device configuration parameters)
5.3 Example for MinTime/MaxTime logic
Example#1 based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V
MaxTime MaxTime
Sleeping(MinTime)
Sleeping(MinTime)
Description Device CmdID
Device
Type
NetvoxPayLoadData
ConfigReport
Req
R718B2
0x01
0x14
MinTime
(2bytes Unit:s)
MaxTime
(2bytes Unit:s)
BatteryChange
(1byte Unit:0.1v)
TemperatureChange
(2byte Unit:0.1℃)
Reserved
(2Bytes,Fixed 0x00)
ConfigReport
Rsp
0x81
Status
(0x00_success)
Reserved
(8Bytes,Fixed 0x00)
ReadConfig
ReportReq
0x02
Reserved
(9Bytes,Fixed 0x00)
ReadConfig
ReportRsp
0x82
MinTime
(2bytes Unit:s)
MaxTime
(2bytes Unit:s)
BatteryChange
(1byte Unit:0.1v)
TemperatureChange
(2byte Unit:0.1℃)
Reserved
(2Bytes,Fixed 0x00)
Wake up and collects data
REPORTS 3.6V
Wakes up and collects data
REPORTS 3.6V
Wakes up and collects data
REPORTS 3.6V