107NetBotz Appliance User’s Guide
Wireless Sensor Setup
Use the Wireless Sensor Setup icon to configure the Coordinator, and add or modify the wireless sensors
in your wireless sensor network.
The NetBotz Wireless Sensor Pod 180 and the NetBotz USB Coordinator & Router connect to a NetBotz
Room Monitor 455 and NetBotz Rack Monitor 450, 550, or 570, allowing you to monitor the
temperature and humidity in a rack in your data center. Additional sensors, required with the USB
Coordinator & Router, allow you to monitor multiple temperature readings, and, on the NetBotz
Wireless Sensor Pod 180, rack door access and a dry contact.
The NetBotz Rack Monitor 450 supports a total of 26 wireless devices (the Coordinator plus 25 devices)
in a wireless sensor network.
The NetBotz Room Monitor 455, and the NetBotz Rack Monitor 550 and 570 each support total of 48
wireless devices (the Coordinator plus 47 devices) in a wireless sensor network.
Supported wireless devices
The following wireless sensors are supported on the wireless sensor network:
NetBotz Wireless Sensor Pod 180
NetBotz USB Coordinator & Router
NetBotz Wireless Temperature Sensor
The following wireless sensors can be configured as the Coordinator or a Router on the wireless sensor
network:
The following wireless sensors can be configured as End Devices on the wireless sensor network:
Sensor Name Range Part Number
Wireless Sensor Pod 180 100 ft - line of sight NBPD0180
USB Coordinator & Router 100 ft - line of sight NBWC100U
Sensor Name Range Part Number
Wireless Sensor Pod 180 100 ft - line of sight NBPD0180
Wireless Temperature Sensor 100 ft - line of sight NBWS100T
NBWS100H