User manual

LED Indicators 22
Doc: HMSI-168-92 Rev: 3.00Netbiter EasyConnect Gateway User Manual
3.4 Netbiter EC310
WhenpowerisappliedalltheLEDindicatorswillbelitwhilethegatewayisstartingup.
Afterthestartupsequencehascompletedtheywillindicatesystemstatus.
3.4.1 RS485 / RS232
3.4.2 Uplink/WAN
3.4.3 Gateway
3.4.4 Power
Indication Meaning
Off RS485 / RS232 port not in use
Green (steady) RS485 / RS232 port enabled in Netbiter Argos
Red (steady) Port failure
Contact Netbiter support.
Green (steady) Connected to Netbiter Argos
Red (steady) Invalid network settings
DHCP: Check that there is a working DHCP server on the network.
Static IP: Check that the IP address, default gateway and DNS are correctly set.
If a proxy is used, check that the proxy settings are correct.
Red (flashing) No connection to Netbiter Argos
Check the network settings.
If a proxy is used, check that the proxy settings are correct.
Check that port 443 is open in the firewall.
Indication Meaning
Off No power, or unit is starting up
Green (steady) Unit is operating normally
Green (flashing) Firmware update in progress
Red (steady) Hardware failure
Contact Netbiter support.
Red (flashing) Application failure
Contact Netbiter support.
Indication Meaning
Off No power
Green (steady) Unit has power