User Guide
SKVF Evaporative Cooler
Modbus Communication Module User Guide
www.neptronic.com
Page | 5
Protocol
Base
Holding
Register
Description
Data Type
Units, Limits, State Texts
Writa
ble
Default Value
6011
406012
Supply High Limit RH Min
Unsigned
Scale 100
Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
W
0% RH
6012
406013
Supply High Limit RH Max
Unsigned
Scale 100
Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
W
0% RH
6013
406014
Supply High Limit RH Bias
Signed
Scale 100
Unit: %, Range: -10% RH to 10% RH
Value x 100 (e.g. 10% RH = 1000)
W
0% RH
6014
406015
Run Time (0)
Unsigned
Scale 100
Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 10 h = 1000)
RO
0h
6015
406016
Run Time (1)
Units: Hours (h), Range: 0 to 2147483647 h
6016
406017
Run Time (2)
Units: Hours (h), Range: 0 to 2147483647 h
6017
406018
Run Time (3)
Units: Hours (h), Range: 0 to 2147483647 h
6018
406019
On Time (0)
Unsigned
Scale 100
Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 10 h = 1000)
RO
0h
6019
406020
On Time (1)
Units: Hours (h), Range: 0 to 2147483647 h
6020
406021
On Time (2)
Units: Hours (h), Range: 0 to 2147483647 h
6021
406022
On Time (3)
Units: Hours (h), Range: 0 to 2147483647 h
6022
406023
Water Treated Volume (0)
Unsigned
Scale 100
Units: Litres (l), Range: 0 to 9999999 l
Value x 100 (e.g. 10 h = 1000)
RO
0l
6023
406024
Water Treated Volume (1)
Units: Litres (l), Range: 0 to 9999999 l
6024
406025
Water Treated Volume (2)
Units: Litres (l), Range: 0 to 9999999 l
6025
406026
Water Treated Volume (3)
Units: Litres (l), Range: 0 to 9999999 l
6026
406027
Service On Time (0)
Unsigned
Scale 100
Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 10 h = 1000)
RO
0h
6027
406028
Service On Time (1)
Units: Hours (h), Range: 0 to 2147483647 h
6028
406029
Service On Time (2)
Units: Hours (h), Range: 0 to 2147483647 h