Instruction Manual
Appendix A: OptiLogic Technical Specifications Pointe Controller User Guide
266
Technical Specifications
Card Cage Power Required 400 mA
Inputs (all) 4
Pulse Inputs 2
Status Indicators Logic Side LED
Counting Modes Pulse & Direction, Up/Down Count, Quadrature
Count Value 32 Bit Signed
Frequency Data 16 Bit Signed (configurable for 1 sec or 200 msec)
Input Signal Type Sinking, sourcing, or differential
Input Impedence 2.0K ohms nominal
Input frequency (on pulses) 80/160 KHz maximum
Min. Input On Voltage
(or differential)
4.00V
Min. Input Off Voltage
(or differential)
3.00V
Maximum Input Voltage 28V
Outputs 2
Output Type Open collector
Commons 1 (connected internally)
Terminal Strip Plug In (removable)
Terminal Screws Slotted (0.1” blade max.)
Max. terminal wire gauge 18 AWG (use copper conductors)
Terminal block torque 2.2 lb-in
Required Temp. rating of
field installed conductors
60°C / 75°C
Weight 1.24 oz (35g)
Type 82
Subtype 2