Manual

Optimation, Inc.
(256)883-3050 31
www.optimate.com
OptiLogic Series
OL2602 Dual RS232 Module
Communication Ports 2
Card Cage Power
Required
110 mA
Type RS232C Status Indicators LEDs for TX and RX
Baud Rates
1200, 2400, 4800,
9600, 19,200
(selectable)
System limitations *See below
Parity Even, odd or none
Max. Terminal Wire
gauge
18 AWG (use copper
conductors)
Data bits 7 or 8 Terminal Strip Plug In (removable)
Transmit buffer 48 bytes Terminal Screws
Slotted (0.1 blade
maximum)
Receive buffer 48 bytes
Required Temperature
rating of field installed
conductors
60C/75C
Weight 1 oz (29g) Terminal block torque 2.2 lb-in
Type 112 Subtype 1
Terminal (each port)
1 Signal
ground
2 Transmit
3 Receive
* For OL4058 ethernet base a maximum of one OL2602 modules may be used. It must be placed in slot 0. For the
OL4054 ethernet base, a maximum of two OL2602 may be used. They must be placed in slots 0 and 1.
1
1
2
2
3
3
Opti
Logic
OptiOptiOptiOptiOpti
OL2602
TX
RX
TX
RX
3
3
2
2
1
1
TX
TX
RX
RX
Signal Gnd
Signal Gnd