Manual

Optimation, Inc.
(256)883-3050
28
www.optimate.com
OptiLogic Series
OL2304 Four Channel Voltage Output
Outputs 4
Card Cage Power
required
700mA
Output Ranges
0-5V, 0-10V, +/-5V, +/-10V
(individual channel
configurable)
External Power
required
none
Resolution 12 bit (1 in 4096) Output current +/-5mA
Output type
Single ended, 1
common
Short circuit current +/-15mA
Offset calibration
error
+/-8 counts @ +/-10V
+/-16 counts @ +/-5V
+/-16 counts @ 0-10V
+/- 32 counts @ 0-5V
Max terminal wire
gauge
18 AWG (use copper
conductors)
Nonlinearity +/- 1 count Terminal strip Plug In (removable)
Load impedence 2Kohm mimimum Terminal screws
Slotted (0.1 blade
max)
Terminal block torque 2.2 lb-in
Required Temperature
rating of field installed
conductors
60C/75C
Type 25 Subtype 1
The OL2304 analog output module is range configurable, on a channel by channel basis, to any of four common
output ranges. Each channel can be configured, via software for either 0-5V, 0-10V, +/-5V or +/-10V ranges. The
module generates its own isolated output power supply, eliminating any need for an outside source.
Terminal Terminal
1 Common 5 Common
2 Out 1 6 Out 3
3 Common 7 Common
4 Out 2 8 Out 4
8
7
6
5
4
3
2
1
Channel 4
Channel 3
Channel 2
Channel 1
+
+
+
+
-
-
-
-