Manual

Optimation, Inc.
(256)883-3050 21
www.optimate.com
OptiLogic Series
OL2211 AC Digital Input Module
Inputs 8
Card Cage Power
Required
60 mA
Input Type AC Optocoupled Status Indicators Logic side LED
Voltage Range 80 - 132 VAC Input Impedance 47K
Min. On Current (per
point)
1.7 mA Commons 2 (connected internally)
Max. On Current (per
point)
2.8 mA Terminal Strip Plug In (removable)
Terminal Screws
Slotted (0.1 blade
max.)
Max terminal wire
gauge
18 AWG (use copper
conductors
Required Temperature
rating of field installed
conductors
60C/75C
Weight 1.3 oz (38g) Terminal block torque 2.2 lb-in
Type 1 Subtype 2
The OL2211 AC Digital input module senses up to eight (8) AC input signals. All inputs are individually
optocoupled for isolation. Filtering is provided for zero crossover. Individual LED indicators provide visual
feedback of current status.
10
9
8
7
6
5
4
3
2
1
80-132VAC
IN7
IN6
IN5
IN4
IN3
IN2
IN1
IN0
module internal
circuit
optical
isolation
To
OptiLogic
processor
Terminal Terminal
1 Common 6 In 3
2 Common 7 In 4
3 In 0 8 In 5
4 In 1 9 In 6
5 In 2 10 In 7
1
2
4
5
6
7
8
9
10
3
0
2
3
1
4 5
6
7
L
OO
2211
I
N